Manolia Group provides fire sprinkler systems in Dubai Production City (formerly IMPZ), coordinating drawings and inspections with Dubai Civil Defence and connections with Dubai Electricity & Water Authority. Dubai Production City, formerly the International Media Production Zone, is a free zone near Al Khail Road combining residential and office towers with light industrial and media-production facilities.

Fire sprinkler systems in Dubai Production City (formerly IMPZ): local context

Dubai Production City, formerly the International Media Production Zone, is a free zone near Al Khail Road combining residential and office towers with light industrial and media-production facilities. It was largely developed from the mid-2000s. Manolia completed MEP for a 2B+G+15 tower with gym here. Plots here are mid-sized and tightly spaced, with towers sharing service roads and neighbouring construction sites.

  • Projects fall under the Dubai Development Authority (DDA) approval channel, with Civil Defence review of fire and life safety systems.
  • Office and media spaces require flexible electrical distribution, UPS-backed circuits and dedicated cooling for equipment-heavy rooms with high sensible loads.
  • The area is inland and dusty, so condenser cleaning and filter access are planned into the design.

Building types we serve in Dubai Production City (formerly IMPZ)

For office buildings, the work concentrates on VAV or FCU zoning for flexible floor plates, tenant fit-out interfaces, energy metering and BMS integration.

Approvals and authorities in Dubai Production City (formerly IMPZ)

Fire sprinkler systems in Dubai Production City (formerly IMPZ) sits within Dubai's regulatory framework. The authorities you will meet are:

  • Dubai Civil Defence (DCD)
  • UAE Fire & Life Safety Code of Practice (UAE FLSC)
  • Dubai Development Authority (DDA)
  • Dubai Electricity & Water Authority (DEWA)
  • Al Sa'fat — Dubai Green Building Evaluation System (Al Sa'fat)

Scope of work

  • Installation of risers, floor control valve assemblies with flow and tamper switches, drain and test stations, and zone isolation so floors can be serviced without shutting the building.
  • Installation of grooved and threaded branch pipework with seismic-style restraint and hanger spacing to the approved standard, plus flexible drops where ceiling coordination demands it.
  • Hydrostatic pressure testing of every section, flushing of mains before head connection, and witnessed pump performance tests against the rated curve.
  • Interface with the fire alarm system so flow switches, valve monitoring and pump running and fault signals report to the fire alarm panel and, where required, the monitoring link.

Systems we install

  • Electric, diesel and jockey fire pump packages with listed controllers and automatic transfer.
  • Pressure-reducing valve stations for high-rise pressure zoning on tall risers.

UAE site and climate challenges

  • Fire water tanks on roofs and in exposed pump rooms can reach high temperatures in summer, encouraging bacterial growth and corrosion. We specify insulated or shaded tanks, coated internals and ventilated pump rooms so stored water and diesel engines stay within manufacturer limits.
  • Diesel fire pumps lose output in high ambient air and hot plant rooms. We check engine derating against summer room conditions near 46–50°C and size ventilation and radiator airflow so the pump still meets its rated duty when the room is hottest.
  • Grooved versus threaded pipework: grooved systems install faster and simplify future modification, while threaded small-bore branches suit tight ceiling voids; most projects use a combination by pipe size.

Relevant Manolia projects

2B+G+15 residential tower, IMPZ

Dubai Production City (formerly IMPZ) · MEP · Completed

Full MEP package for a two-basement residential tower with gym.

G+6 building with health club, DSO

Dubai Silicon Oasis (DSO) · MEP · Completed

Full MEP package delivered.

Frequently asked questions

Which authorities approve fire sprinkler systems in Dubai Production City (formerly IMPZ)?

Approvals in Dubai Production City (formerly IMPZ) typically involve Dubai Civil Defence, UAE Fire & Life Safety Code of Practice, Dubai Development Authority and Dubai Electricity & Water Authority. Exact routes depend on the plot, the master developer and whether the site sits in a free zone, so we confirm the authority matrix during mobilisation and prepare submissions accordingly.

What similar work has Manolia completed near Dubai Production City (formerly IMPZ)?

Relevant reference work includes 2B+G+15 residential tower, IMPZ (MEP, completed). Each reference is listed with its scope and status as recorded in our company profile.

Can existing sprinkler systems be modified during a fit-out?

Yes, but the zone must be isolated, drained and the change shown on drawings for approval where the layout changes materially. Head positions are adjusted to the new partitions and ceilings, the section is pressure tested again and the fire alarm interface is checked before the zone returns to service.

Next chapter

Tendering a building or MEP package?

Developers, main contractors and consultants: send drawings, BOQs or an RFQ to our engineering team. We review every enquiry and respond with a clear scope and programme.

Request a prequalification pack Send a project enquiry